. No person shall build or rebuild any subway, manhole,
chamber, or underground room used or to be used to contain, encase,
cover, or conduct any wire, cable, or appliance, to conduct or handle
electricity, unless such subway, manhole, chamber, or underground
room has an inside measurement of not less than four feet at the
maximum points between the side walls thereof, and between the end
walls thereof, and not less than five feet at all points between the
floor and the top or ceiling thereof, or if circular in shape, at
least four feet diameter inside measurement and not less than five
feet at all points between the floor and ceiling thereof. This
section does not apply to any such subway, manhole, chamber, or
underground room, within which it is not intended or required that
any human being perform work or labor or be employed. This section
does not apply where satisfactory proof is submitted to the
commission that it is impracticable or physically impossible to
comply with this law within the space or location so designated by
the proper municipal authorities.